Procedural Considerations
Page 66 34-ST-25-20 MC Toolkit User Manual Release 0
7/03
Table 21 Calibration - Apply Values (non-Honeywell Transmitter)
Calibration - Apply Values (non-Honeywell Transmitter)
Overview of
Objectives
· Manually set Process Variable input to 0%, and apply this value to Set LRV (output) at 4
MA.
· Manually set Process Variable input to 100%, and apply this value to set URV (output) at 20
mA.
Apply
Values
(4mA - LRV)
Select Apply Values.
Select 4mA.